KYORITSU ANALOG INSULATION / CONTINUITY TESTER

$434.50

 

Description

KYORITSU ANALOG INSULATION / CONTINUITY TESTER

MODEL 3132A

• Dust and Drip-proof construction (designed to IEC 60529 IP54)
• Designed to meet IEC 61010-1 and IEC 61557 safety standard
• 1mA rated test current at the minimum resistance
• 200mA measuring current on continuity testing
• Automatic discharge of circuit capacitance
(Any charge stored in the circuit under test will be automatically discharged after testing)
• Live circuit warning buzzer and neon lamp
• Small and lightweight. Shock resistant new case material
• AC voltmeter with linear, easy-to-read scale
• Operates on AA, R6 × 6 dry batteries

Insulation Resistance

Test voltage 250/500/1000V
Measuring ranges<br>(Mid-scale value) 100/200/400MΩ
(1/2/4MΩ)
Output voltage on open circuit Rated test voltage+20%, -0%
Nominal current 1mA DC min.
Output short circuit current 1 – 2mA DC
Accuracy 0.1 – 10/0.2 – 20/0.4 – 40MΩ
(Accuracy Guaranteed Ranges) ±5% of indicated value

Continuity

Measuring ranges<br>(Mid-scale value) 3/500Ω
(1.5/20Ω)
Output voltage on open circuit Approx. 4.1V DC
Measuring current 210mA DC min.
Accuracy ±1.5% of scale length

AC Voltage

AC Voltage 0 – 600V AC
Accuracy ±5% of scale length

General

Safety Standard IEC 61010-1 CAT III 600V Pollution Degree 2
IEC 61010-2-034, IEC 61557-1,2,4
IEC 61557-1/2/4
IP Rating IEC 60529-IP54
EMC Standard IEC 61326-1
Power source R6 (AA) (1.5V) × 6
Dimension 106(L) × 160(W) × 72(D)mm
Weight Approx. 560g
Accessories 7122B (Test leads)
9074 (Cord case)
8923 (Fuse[0.5A/600V]) × 1 (included), 1 (spare)
R6 (AA) × 6
9121 (Shoulder Strap)
Instruction Manual

 

3005A_07A_3131A_32A-E-KEW1